Inert Gas: Coping with Oxygen Deficient Environments in 400 Area

1979? film, with transcript

Catalog description: Safety training video about inert gas environments, e.g. Argon and Nitrogen from the FFTF areas. Originally part of the CRBRP.

This is film 7479946 in our catalog.

Show transcript
00:00 While working at the FFTF you find yourself about to enter a confined space marked by this sign.
00:26 The sign is there to inform you that there is a possibility of that space becoming oxygen
00:32 deficient. Would you know what to do in this situation? In two breaths to you learn some
00:48 general information about oxygen deficient spaces. If you walk into an oxygen deficient atmosphere
00:54 you won't have a single warning and it's too late to hold your breath. You'll take two breaths and
01:00 you'll collapse. In this presentation, we will look at two types of inert gas found in the FFTF
01:07 which can displace oxygen, the precautions which are taken in the plant to cope with oxygen
01:13 deficient environments, and some procedures which you should know when working in a space which
01:18 could become oxygen deficient. Argon and nitrogen are inert gases. This means they have little
01:25 or no ability to interact chemically with other substances. Because of this, they are
01:31 used to separate or inert potentially volatile materials. Argon is used as a cover gas and
01:38 as a buffer between seals in various places throughout the FFTF.
01:47 Since it is heavier than air, any argon that might leak may sink and concentrate in low-lying
01:53 areas.
01:56 Nitrogen is used for valve actuation, to inert primary sodium cells, and to flood secondary
02:07 sodium cells in an emergency situation nitrogen is a light gas which mixes
02:13 freely with air it may be found at all levels these gases are not in themselves
02:18 toxic they are hazardous because they displace the oxygen which is necessary
02:23 for life the normal amount of oxygen found in air is 21% the minimum amount
02:30 of oxygen necessary for a work atmosphere at Hedl has been established
02:34 at 19.5 percent. This is very conservative since physical effects are not perceivable
02:41 above 16 percent oxygen. However, all monitors in use at the FFTF have their alarm set at
02:48 the 19.5 percent level. Entry into a space with less than 19.5 percent oxygen requires
02:56 use of approved respiratory protection and compliance with administrative procedure.
03:03 oxygen monitors are situated at the FFTF in the following
03:07 locations. Areas where there is a high potential of an inert gas
03:12 leak, such as a secondary sodium cell, and in areas where there
03:16 is little ventilation or air circulation. That is where the
03:19 air is changed less than one and a half times per hour. As
03:24 previously stated, these monitors react to the 19.5%
03:28 oxygen level. When this level is reached, an alarm will go off.
03:33 And if the monitor is located in a high noise area, a rotating beacon will also be activated.
03:46 In addition to having permanent oxygen monitors, all cells in the FFTF will be marked by this
03:51 sign.
03:54 Requirements for access to the space will be indicated on the sign.
03:57 The degree of oxygen deficiency potential in the space will determine what actions are
04:02 required.
04:04 Common requirements include use of personal oxygen monitors, use of the buddy system,
04:11 use of additional ventilation equipment, notification of the control room, and a five-minute escape
04:18 pack available for immediate use.
04:21 Let's take a closer look at these requirements.
04:24 There are two types of personal oxygen monitors in common use at the FFTF.
04:29 The Gastek OX80 is the most commonly used.
04:33 It is worn at waist level, and its alarm is a loud buzzing sound.
04:42 When the Gastek is switched on, this alarm will sound briefly, to let you know it is
04:50 operating properly.
04:52 If the alarm continues, sounding intermittently, it is a signal that the battery is low and
04:59 needs recharging.
05:02 To check oxygen levels in the space surrounding you, press the button near the readout window.
05:08 The level will be shown in digital figures.
05:12 The Edmont-Wilson monitor is also worn at waist level.
05:16 This alarm is a high-pitched whistle.
05:23 If the alarm sounds when the Edmont Wilson is first turned on,
05:28 it is an indication the battery is low.
05:31 The sensor for the Edmont Wilson is attached to an extension cord.
05:35 It may be lowered into a cell prior to entry in order to check oxygen levels.
05:41 Once again, these personal monitors have their alarms set at the 19.5 percent level.
05:47 When an alarm goes off, take immediate action.
05:53 Oxygen monitors are your first line of protection.
05:55 Believe what they tell you and make certain you know how to operate them.
06:00 The buddy system is a well-known preventative measure, which has saved thousands of lives.
06:06 In this instance, one person must remain outside the space and maintain either visual or verbal
06:11 contact with their partner.
06:15 Additional ventilation for confined spaces may be provided by such equipment as portable
06:19 blowers and flexible hose.
06:22 Another means of letting others know your whereabouts is to call the control room prior
06:26 to entry.
06:29 If this procedure is posted, you must also notify the control room and confirm your departure
06:34 you leave. Know when and how to use a five-minute escape pack. Before using,
06:40 check the gauge on the unit to ensure it is charged properly. If an oxygen monitor
06:46 alarm goes off, don the escape pack immediately. Open the case, pull out the
06:52 unit, unfold the mask, pull the ring. If you hear a hiss, the unit is working
07:03 properly. Pull the mask over your head, adjust the next seal, and then the drawstring. The yellow tab
07:13 tightens and the red tab loosens. An important point to remember is that the escape pack is to
07:20 be used for escape only. It is not to be used for rescue purposes. In an emergency situation,
07:28 your job is to get out and warn others.
07:31 Don't become a victim yourself by trying to rescue someone without the proper equipment.
07:37 Call the control room, and the emergency response team will initiate a rescue action.
07:42 The most important aspect of safe entry into a confined space is your knowledge of safety
08:02 procedures. When you are to work in a confined space, remember argon and nitrogen may cause a
08:09 hazard by displacing oxygen in the air. Permanent oxygen monitors are situated in all normally
08:16 accessible spaces, which might become oxygen deficient. Signs are posted at the entrances
08:22 to all confined spaces, listing requirements for entry. Heed the requirements and, if you
08:28 are wearing a personal oxygen monitor or five-minute escape pack, know how and when to use them.
08:34 When an oxygen monitor alarm sounds, immediately don the five-minute escape pack, leave the
08:41 area and notify the control room.
08:49 You are the most important part of any safety program.
08:52 Your knowledge and use of safety procedures will go a long way in helping to keep the
08:57 FFTF a good place to work.